- HW-1088 Positioning Leakage Detection Module
- Model:71×88×58.5mm
- Update:2012-04-10
- Hits:
- 可監控長達1500米的BTR水浸感應線,RS485接口,采用MODBUS RTU協議與監控系統通信
- favorite
- Description
Product Overview
??? HW-1088 leak positioning monitoring module can be monitoring the BTR for 1500 meters Leach sensing line,once detect liquid, It will positioning leak position which displayed by LED and produce the sound-sight alarm. Also the position will be sent to the monitoring system by RS485 interface. HW-1088 adopts MODBUS RTU MODBUS RTU protocol to communicate with the monitoring system, so users can integrate the HW-1088 into different system conveniently.
?Function and Characteristics
???????? One way of sensing line interface, monitoring with 1500 meters induction line
???????? The alarm status is displayed by LED
???????? Four digital pipe display leak position
???????? Provide all relay modules, often open/closed switch alarm signal to expand the external alarm system
???????? As many as 40 alarm log storage space, convenient for users to inquires the historical alarms events
???????? 12-30VDC / 9V - 25VAC wide range of working voltage
???????? Simple twisted-pair cable RS485 communication, Communication distance up to 1000 meters
???????? Software setup the communication address and parameters.
???????? The Convenient DIN guide installation way
Working Conditions
???????? Power: DC12V—DC30V/AC9V--AC25V???? Power consumption less than 3W
???????? Working Temperature: Fahrenheit zero to 50 degrees Celsius
???????? Work Humidity: 10% ~ 90% RH; No condensation
???????? Atmospheric Pressure: 86 ~ 106 kpa
Technical Parameters
???????? Communicationparameters: 2400/4800/9600/19200bps, 1 stop bits, no parity bit, default 9600
????Communication Address:o-255, node number less than 32(default address 0).
????Positioning accuracy: cable of the presidents of plus or minus 0.6 meters 0.5%.
????Alarm Output: relay type,often open or closed; Open-circuit impedance more than 100 ohms; short-circuit impedance less than 100 ohms.
????Adherent point is pressure-proof: 30 volts direct current/1 ampere; 60 volts direct current/0.3 ampere; 125 volts direct current/0.5 ampere.
?